Gas tightness testing on commercial premises: when and why

Commercial engineers covering Suffolk, Essex and Cambridgeshire

Winter gas safety: smell gas? Call National Gas Emergency on 0800 111 999. For commercial boiler breakdowns call 0800 0996 007.

A gas tightness test is needed on commercial premises whenever gas pipework is new, altered, extended or re-used, before work on existing pipework, when a gas leak is known or suspected, after the supply has lost pressure completely (for example when the emergency control valve has been shut), immediately before pipework is purged, and as routine testing of existing pipework. Those are the circumstances listed in the scope of the IGEM testing procedures IGE/UP/1 and IGE/UP/1A, and the law adds that anyone who works on installation pipework "which might affect the gastightness of any part of it" must have that part "adequately tested to verify that it is gastight" immediately afterwards. On commercial premises the test is carried out by a Gas Safe registered engineer qualified for the work, never by site staff. This guide explains what a tightness test is, when it is needed, which IGEM procedure applies to your installation, and what duty holders and facilities teams should do.

A team of over 10 local engineers to call on · Gas Safe 985448 · Call 0800 0996 007 · WhatsApp 07947 578332

Commercial heating tips and advice · · Fast Commercial Boiler Help, Gas Safe 985448

What a gas tightness test is

A tightness test checks that a section of gas pipework, including any meter and appliance pipework within the test, is not leaking. IGEM explains that "the terms "soundness testing" (as used in IGE/UP/1 Edition 1) and "tightness testing" have an identical meaning", so you may see either phrase on older paperwork and in manufacturers' manuals.

It is different from a strength test. IGEM says strength testing "has been introduced for new pipework and extensions to ensure that pipework can withstand, with respect to integrity, the pressures it could experience under fault conditions", and that as a result "the subsequent tightness test is carried out at operating pressure (OP)". In short, new pipework and extensions are usually strength tested and then tightness tested; existing pipework is normally tightness tested. Purging, which removes air (or gas) from the pipework safely, is a separate step that follows the testing when gas is being supplied.

When is a gas tightness test needed? The circumstances IGEM lists

The scope of IGE/UP/1 Edition 2 (often written IGEM/UP/1) says its procedures apply to strength and tightness testing of pipework "of any diameter in the following circumstances". IGE/UP/1A Edition 2 lists the same circumstances for smaller installations. In plain terms:

Most of these are triggered by work on the gas installation, so they are usually part of a job your engineer is already doing: an installation, an alteration, a repair or a service. The two that facilities teams most often need to act on are a suspected leak and a supply that has been turned off at the emergency control valve.

What the Gas Safety Regulations require

The Gas Safety (Installation and Use) Regulations 1998 put the testing duty on the person doing the work:

Manufacturers say the same thing in their own words. Ideal's Evomax 2 commercial boiler manual says "The complete installation MUST be tested for gas soundness and purged in accordance with the appropriate standards listed on page 8", lists IGEM/UP/1 among those standards, and tells the engineer that after servicing or replacing components they should always "Test for gas soundness."

Which IGEM procedure applies to your installation?

IGEM publishes different testing procedures for different sizes and types of installation, and the engineer has to check which one fits before testing. IGEM says "It is necessary to check the scope of referenced standards before proceeding."

ProcedureWhat its scope covers (as IGEM describes it)
IGE/UP/1A Edition 2Strength and tightness testing and direct purging of Natural Gas installations on industrial and commercial premises with a volume not exceeding 1 m³ (including any meter and an allowance for fittings), an MOP not exceeding 40 mbar at the outlet of the primary meter regulator, a supply MOP not exceeding 75 mbar, and a nominal bore not exceeding 150 mm. Measured from the outlet of the emergency control valve.
IGE/UP/1 Edition 2Strength and tightness testing and direct purging of pipework with a maximum operating pressure (MOP) not exceeding 16 bar, for Natural Gas from the outlet of the emergency control valve, and for LPG from the outlet of the bulk storage vessel or cylinder valve. IGE/UP/1A says that for a volume over 1 m³, an MOP over 40 mbar, a supply MOP over 75 mbar or a nominal bore over 150 mm, "IGE/UP/1 applies".
IGE/UP/1BDomestic-sized Natural Gas installations. IGEM says IGE/UP/1A "can be used for pipework exceeding 28 mm diameter on domestic premises".
LPGA TM-62Tightness testing of domestic-sized LPG pipework (volume not exceeding 0.02 m³). IGEM says "For greater volume, IGE/UP/1 Edition 2 applies."

The design and installation of the pipework itself is covered by a separate standard, IGEM/UP/2 Edition 4, which covers the "design, installation, commissioning, operation, maintenance and decommissioning" of installation pipework on industrial and commercial premises with an MOP not exceeding 60 bar. IGEM notes that BS 6891 "may be utilised on smaller commercial premises that are within its scope". Which documents apply is a decision for your engineer, and it should be clear from their test certificate.

Routine tightness testing and records

IGEM lists "routine testing of existing pipework" as one of the circumstances its procedures cover, but the scope pages do not set a fixed interval. IGEM/UP/2 says that for existing industrial and commercial installations, the Dangerous Substances and Explosive Atmosphere Regulations (DSEAR) "require the completion of a risk assessment", and that "it is essential that they are maintained and inspected as determined by the risk assessment." In practice, agree with your engineer how routine testing fits into your commercial gas safety inspection and planned maintenance, and remember that a boiler service normally ends with a gas soundness check of the appliance (see what a commercial boiler service includes).

IGEM sells blank triplicate certificate pads for strength testing, tightness testing and direct purging to the IGE/UP/1 and IGE/UP/1A procedures, so ask for a written record of each test and keep it with your other gas safety paperwork. Our guide to heating maintenance records explains how to file them so insurers, landlords and auditors can find them.

What site staff should do (and not do)

A tightness test means isolating the gas, pressurising pipework and reading test gauges, and it is followed by purging. That is gas work, and it is for a Gas Safe registered engineer qualified for commercial work only. Site and facilities staff have a different, equally important job:

Who does what

TaskWho
Report a smell of gas, shut off the supply and call the emergency numberAnyone on site, following HSE's advice and your site procedure
Keep the emergency control valve accessible and know where it is; log supply interruptions and works near gas pipeworkTrained site or facilities staff
Strength testing, tightness testing and purging to IGE/UP/1 or IGE/UP/1A; testing appliance connections; relighting and checking appliancesGas Safe registered engineer qualified for commercial work
Design, installation and alteration of gas pipework to IGEM/UP/2 (or BS 6891 where within scope)Gas Safe registered engineer qualified for commercial work
Make sure gas pipework is maintained in a safe condition, the people doing gas work are competent, and records are keptThe employer or self-employed person in control of the premises (the duty holder)

Duty holder responsibilities

Regulation 35 of the Gas Safety (Installation and Use) Regulations 1998 requires every employer or self-employed person to ensure that "any gas appliance, installation pipework or flue installed at any place of work under his control is maintained in a safe condition so as to prevent risk of injury to any person." Regulation 3(1) says "No person shall carry out any work in relation to a gas fitting or gas storage vessel unless he is competent to do so", and regulation 3(2) extends the duty to every employer and self-employed person who "has required such work to be carried out at any place of work under his control".

HSE says that in workplaces such as "shops, restaurants, schools and hospitals, work on gas fittings must be carried out by a Gas Safe registered engineer who is qualified to do the work", and that "It’s your responsibility to check a person is registered and is qualified." In factories and certain other premises HSE says the work must be done by a competent person. Our guide on how to check a Gas Safe engineer is qualified for commercial work shows how to check the right categories on an engineer's ID card.

Need gas pipework tested?

If you have had work done near your gas pipework, are planning a new appliance or a commercial boiler installation, run on LPG, or the gas has been turned off at the emergency control valve, call us on 0800 0996 007 or WhatsApp 07947 578332. Our Gas Safe registered engineers (Gas Safe 985448) carry out commercial gas safety inspections and gas safety work on commercial premises. If you smell gas now, call the National Gas Emergency Service on 0800 111 999 first.

Safety note

Under the Gas Safety (Installation and Use) Regulations 1998, gas work must be carried out by a Gas Safe registered engineer, and we apply that rule on every site. Don't attempt DIY work on gas appliances, burners, flues or safety devices. On pressure systems, trained site staff should stick to visual and gauge checks, log the readings and report anything abnormal. Never adjust, cap, plug or test-lift a relief valve yourself.

Talk to a Gas Safe commercial engineer

Fast Commercial Boiler Help is a Gas Safe registered (985448) commercial heating business based at 4 Market Hill, Clare, Sudbury, Suffolk CO10 8NN. Our team of over 10 local engineers covers East Anglia and East London, working on commercial boilers, plant rooms, water heaters, and warm air, radiant and unit heaters. We work on commercial premises only.

Call 0800 0996 007

Call or WhatsApp 07947 578332 (a photo of the appliance data plate or the fault display helps) · Email [email protected]

Frequently asked questions

When is a gas tightness test needed on commercial premises?

IGEM's testing procedures IGE/UP/1 and IGE/UP/1A list the circumstances: new pipework; alteration, replacement, re-use or uprating of existing pipework; new extensions; before any work on existing pipework; a known or suspected gas leak; a complete loss of pressure for any reason (for example after the emergency control valve has been closed); routine testing of existing pipework; and immediately before purging. The test must be carried out by a Gas Safe registered engineer qualified for commercial work.

Is a gas tightness test a legal requirement?

Regulation 22 of the Gas Safety (Installation and Use) Regulations 1998 says that anyone who works on installation pipework in a way that might affect its gastightness must immediately ensure that part is adequately tested to verify that it is gastight. Regulation 33 requires a new appliance's connection to the pipework to be tested. IGEM's procedures set out how the tests are done. For routine testing, IGEM/UP/2 says existing industrial and commercial installations should be maintained and inspected as determined by the DSEAR risk assessment.

What is the difference between IGEM/UP/1 and IGEM/UP/1A?

IGE/UP/1A covers smaller, low pressure Natural Gas installations on industrial and commercial premises: a volume up to 1 m³, an MOP up to 40 mbar at the outlet of the primary meter regulator, a supply MOP up to 75 mbar and a nominal bore up to 150 mm. Anything larger, higher pressure or on other gases such as LPG falls under IGE/UP/1, which covers pipework with an MOP up to 16 bar. Your engineer decides which applies.

What is the difference between a strength test and a tightness test?

A strength test checks that new pipework and extensions can withstand the pressures they could see under fault conditions. A tightness test checks the pipework is not leaking and, after a strength test, is carried out at operating pressure. New pipework is usually strength tested then tightness tested; existing pipework is normally tightness tested. Both are gas work for a Gas Safe registered engineer.

Can our maintenance staff carry out a gas tightness test?

No. Testing and purging gas pipework is work on gas fittings. HSE says that in workplaces such as shops, restaurants, schools and hospitals it must be carried out by a Gas Safe registered engineer who is qualified to do the work, and in factories and certain other premises by a competent person. Site staff should report smells of gas, follow HSE's leak advice (turn off the supply and call 0800 111 999 for natural gas) and not turn the gas back on until a competent person has dealt with it.

Sources and further reading

Call 0800 0996 007

Call or WhatsApp 07947 578332 · [email protected]

General guidance only. This article is general information for commercial premises. It is not a substitute for advice from a competent engineer who has seen your site and equipment, or for the manufacturer's instructions. Duty holders remain responsible for their own legal compliance.