Legionella and hot water temperatures in commercial buildings

Commercial engineers covering Suffolk, Essex and Cambridgeshire

Winter gas safety: smell gas? Call National Gas Emergency on 0800 111 999. For commercial boiler breakdowns call 0800 0996 007.

In most commercial buildings, the same plant that heats the building also heats the water. Boilers feed calorifiers, or gas-fired water heaters store hot water for kitchens, washrooms and showers. That means the condition of your heating plant has a direct effect on how well you control legionella. This guide sets out the hot water temperatures HSE expects in commercial buildings, the routine checks behind them, how heating plant problems can undermine them, and what duty holders need to have in place. It is written for facilities managers, building owners and site teams, and it is based on HSE's legionella guidance, the L8 Approved Code of Practice and HSG274 technical guidance.

A team of over 10 local engineers to call on · Gas Safe 985448 · Call 0800 0996 007 · WhatsApp 07947 578332

Commercial heating tips and advice · · Fast Commercial Boiler Help, Gas Safe 985448

Why temperature is the main control

HSE says there is a reasonably foreseeable legionella risk if your water system has a water temperature between 20 and 45°C, creates or spreads breathable droplets (for example from taps and showers), stores or recirculates water, or is likely to contain nutrients such as rust, sludge, scale, organic matter and biofilms. Hot and cold water systems are among the most common sources.

HSE explains that legionella can grow in water systems between 20°C and 45°C, especially where there is a risk of stagnation, and that avoiding that range "for as long as possible is a key control measure." It describes temperature control as "the traditional strategy for reducing the risk of legionella in hot and cold water systems." Other control methods exist, but where temperature is not used, HSE says you still need to show you are achieving effective control.

The temperatures HSE expects

HSE's guidance on hot and cold water systems gives these figures:

WhereTemperature
Hot water storage (calorifier or water heater)Stored at 60°C or above. HSE says outgoing water from calorifiers should be at least 60°C.
Hot water outletsDistributed so it reaches 50°C within 1 minute at the outlets (55°C in healthcare premises).
Hot supply to thermostatic mixing valves (TMVs)At least 50°C within 1 minute of running the water.
Cold waterMaintained, where possible, below 20°C. HSE says cold sentinel taps should be below 20°C after running for 2 minutes.

HSE also says pipe runs downstream of TMVs should not exceed 2m. Hot water is a scald risk as well as a control measure: HSE notes there is a risk of scalding where water comes out of taps above 44°C, and where vulnerable people can get into baths or showers and the risk is significant, a Type 3 TMV must be fitted to stop water being discharged above 44°C. Your risk assessment has to balance both.

How heating plant affects legionella control

The temperatures above depend on the plant producing and circulating enough heat. A few common ways a heating plant fault turns into a water hygiene problem:

When your monitoring shows the stored or return temperature is low, the cause is often on the heating side. Our engineers repair commercial water heaters and calorifiers and the boilers that serve them, and we cover the wider plant room in our commercial plant room safety checklist.

Routine checks HSE suggests for hot water

HSE's "things to consider" page lists typical checks for hot and cold water systems. The right frequency for your site comes from your risk assessment, but HSE's examples include:

CheckHSE's suggested frequency
Calorifier flow and return temperatures (outgoing at least 60°C)Monthly, with findings recorded
Hot water sentinel outlets (at least 50°C within 1 minute)Monthly, plus representative outlets on a rotational basis
Hot water inlet to TMVs, where fittedMonthly
Cold water sentinel outlets (below 20°C after 2 minutes)Monthly
Cold water storage tank temperature at the ball valve outletEvery 6 months
Visual check of calorifier internal surfaces for scale and sludgeWhen possible, and cleanliness checked at least annually
Flushing infrequently used outletsWeekly
Cleaning and descaling showerheads and hosesQuarterly, or as the risk assessment decides

HSE notes that a building management system can take the calorifier measurements if one is installed, and that remote temperature monitoring is increasingly used and allows early detection of control failures. It recommends that remote monitoring is based on a specific legionella risk assessment and agreed by a competent person.

For enclosed hot and cold water systems, HSE says microbiological monitoring is not usually required. Testing for legionella may be necessary where there is doubt about how well the control regime is working, or where recommended temperatures are not being consistently achieved. Where sampling is needed, HSE says it should follow BS 7592 and be analysed by a UKAS-accredited laboratory.

Duty holder checklist

HSE says employers and people in control of premises, including landlords, must identify and assess sources of risk, manage, prevent or control those risks, and keep the correct records. The legal framework is the Health and Safety at Work etc Act, the Management of Health and Safety at Work Regulations and COSHH, with practical guidance in the L8 Approved Code of Practice and HSG274.

Taking calorifier flow and return readings

The monthly calorifier check HSE suggests is simple, but readings are only useful if they are taken the same way each time. A practical routine for site teams:

  1. Use the same points every month. HSE says the thermometer pocket at the top of the cylinder, and on the return leg if fitted, is a useful point for accurate measurement. If you use a contact thermometer on the pipe instead, mark the spot so the next person uses it too.
  2. Read the outgoing (flow) temperature. HSE says outgoing water from calorifiers should be at least 60°C.
  3. Read the return temperature where the system has a circulation loop. HSE describes the flow and return check as making sure the supply and return temperatures on each hot water loop are unchanged, showing the loop is working as required.
  4. Record the date, time and who took the reading, alongside the sentinel outlet checks, so trends show up.
  5. Do not change any settings. If a reading is low, report it to your responsible person.

Reading at a similar time each month helps, because a calorifier just after a heavy draw-off, such as straight after a kitchen's morning wash-down, can read lower than it will an hour later.

What a low reading can point to on the heating side

What the log showsPossible plant-side causes an engineer will check
Flow below 60°C at every checkCalorifier or water heater thermostat set too low or faulty, boiler not prioritising hot water, primary pump or valve fault, boiler short of output or locking out
Flow fine in the afternoon, low first thingTime schedule not giving the calorifier enough heat-up time before demand starts, or boiler off overnight with no hot water priority
Flow fine but return well downSecondary circulation pump stopped or air-locked, a balancing valve out of position, or a long poorly insulated run
Readings falling over several monthsScale on the heat exchanger or coil reducing heat transfer, or a boiler whose combustion is drifting and needs a service
Gas water heater keeps going outIgnition, flame sensing, flue or air supply fault on the appliance itself

These are the faults a Gas Safe registered engineer can find and fix on the plant. The water hygiene side, such as reviewing the risk assessment, flushing and any sampling, stays with your responsible person and water hygiene contractor. HSE also notes that testing for legionella may be needed where recommended temperatures are not being consistently achieved.

Where Fast Commercial Boiler Help fits

Legionella risk assessment, water treatment and sampling are a specialist field, and HSE notes that testing can be carried out by a water treatment company or consultant, or by a trained and supervised operator. Our part is the heating and hot water plant itself. If your responsible person's records show a calorifier or water heater not holding 60°C, a weak return temperature or a unit that keeps locking out, our Gas Safe registered engineers can find and fix the fault on the boilers, water heaters and controls. We also service that plant on a planned preventive maintenance basis, and our guide to water heater pressure relief valve checks covers the safety devices on the same equipment.

Please don't adjust gas water heater or boiler controls to chase a temperature yourself. Talk to your responsible person, because a higher setting changes the scald risk, and get a competent engineer to find out why the plant is underperforming.

Safety note

Under the Gas Safety (Installation and Use) Regulations 1998, gas work must be carried out by a Gas Safe registered engineer, and we apply that rule on every site. Don't attempt DIY work on gas appliances, burners, flues or safety devices. On pressure systems, trained site staff should stick to visual and gauge checks, log the readings and report anything abnormal. Never adjust, cap, plug or test-lift a relief valve yourself.

Talk to a Gas Safe commercial engineer

Fast Commercial Boiler Help is a Gas Safe registered (985448) commercial heating business based at 4 Market Hill, Clare, Sudbury, Suffolk CO10 8NN. Our team of over 10 local engineers covers East Anglia and East London, working on commercial boilers, plant rooms, water heaters, and warm air, radiant and unit heaters. We work on commercial premises only.

Call 0800 0996 007

Call or WhatsApp 07947 578332 (a photo of the appliance data plate or the fault display helps) · Email [email protected]

Frequently asked questions

What temperature should hot water be stored at to control legionella?

HSE says hot water should be stored at 60°C or above and distributed so that it reaches 50°C within 1 minute at the outlets, or 55°C in healthcare premises. Outgoing water from a calorifier should be at least 60°C.

What temperature range does legionella grow in?

HSE says legionella can grow in water systems between 20°C and 45°C, especially where water stagnates. That is why cold water should be kept below 20°C where possible and hot water stored at 60°C or above.

How often should hot water temperatures be checked in a commercial building?

It depends on your risk assessment. HSE's examples include monthly checks of calorifier flow and return temperatures and of sentinel outlets, with findings recorded, plus representative outlets on a rotational basis.

Who is responsible for legionella control in a commercial building?

The employer or person in control of the premises, including landlords. HSE says they must assess and control the risk, keep records and appoint a competent responsible person to take responsibility for controlling the risk.

Can a boiler fault cause a legionella risk?

It can. If the boiler serving a calorifier, or a gas-fired water heater, is faulty or not running as it should, stored hot water may not reach 60°C. A Gas Safe registered commercial engineer should find the fault, and your responsible person should review the monitoring records and the risk assessment.

How do you take a calorifier flow and return temperature?

Use the same measuring points each month, such as the thermometer pocket at the top of the cylinder and on the return leg if fitted. HSE says outgoing water should be at least 60°C, and the return should show the hot water loop is working. Record the date, time and who took it.

What is the right commercial hot water temperature at the taps?

HSE guidance is for hot water to reach at least 50°C within 1 minute at outlets, or 55°C in healthcare premises. Where vulnerable people bathe or shower, thermostatic mixing valves limit the temperature delivered, so a risk assessment must balance scald and legionella risk.

Our calorifier reads below 60°C. Should we turn the thermostat up?

Not yourself. Report it to your responsible person, because the setting affects scald risk too, and ask a competent engineer to find out why the plant is not reaching temperature. Common causes include controls, pumps, scale and boiler faults.

Sources and further reading